La innovación es la base de todo lo que hacemos, pero nuestra verdadera motivación proviene del futuro. Trabajamos arduamente para eliminar las barreras a la energía limpia, haciéndola más práctica y accesible para todos. Para nosotros, esto no es solo un negocio: se trata de crear un mundo sostenible que nos enorgullezca legar a la próxima generación.

Shaw - Director ejecutivo de Future Green Technology Co., Ltd.
C&I PV & Energy Storage Engineering Guide
Circulating Current, Communication Conflicts, and Expansion Design Solutions
A field-proven technical guide addressing root causes of parallel faults, troubleshooting workflows, and standardized phased expansion architecture for weak-grid and off-grid microgrid deployments.
Introduction

In commercial and industrial photovoltaic and energy storage microgrid projects, the power limits of single inverters, redundancy requirements, and the need for phased construction have made parallel operation of multiple inverters the mainstream solution. Parallel operation allows for flexible capacity expansion, improves system redundancy, and ensures that if one inverter fails, the others continue to operate, reducing the overall downtime risk.

However, parallel operation is not simply connecting the AC outputs to the same busbar. Circulating current, communication bus conflicts, power distribution imbalances, and incompatibility with future expansion are the most common faults encountered in overseas projects. These can range from minor issues like reduced power generation and frequent inverter alarms and grid disconnection to more serious problems like burnt-out power devices and triggered grid protection. The risks are even higher in areas with weak grids and in off-grid microgrids. This article breaks down the root causes of these faults, provides practical troubleshooting solutions, and outlines standardized expansion design principles.

SECTION I Circulating Current in Parallel Systems: Causes, Hazards, and Suppression Solutions

Circulating current refers to the internal circulating current flowing between inverters that is not supplied to the load. It is the primary pain point in parallel systems.

1. Causes of Circulating Current
1. Inconsistent Output Voltage Amplitude, Phase, and Frequency: Even with the same model of inverter, variations in device parameters, sampling errors, and line impedance can lead to voltage vector differences, forming voltage difference-driven circulating current. This phenomenon is particularly pronounced in off-grid VF parallel mode.
2. Carrier Asynchrony: Mismatched PWM carrier phases between inverters generate high-frequency switching circulating current, causing heat generation, electromagnetic interference, and interference with the communication bus.
3. Inconsistent AC Outgoing Line Length and Diameter: Impedance mismatch in the cables from the two inverters to the AC combiner cabinet leads to load sharing failure and continuous generation of active/reactive circulating current.
4. Grounding Unequal Potential: The dispersed grounding points of multiple inverters and the lack of equipotential bonding between PE lines increase common-mode circulating current, a key risk point emphasized in the SUN2000 parallel connection scheme.
2. Field Hazards Caused by Circulating Current
  • Continuous overheating of inverter IGBTs and inductors, resulting in reduced power output and decreased power generation revenue;
  • Frequent false alarms from leakage protection and insulation alarms;
  • Harmonic amplification, failing to meet local power quality standards, leading to grid connection acceptance failure;
  • In extreme cases, the continuous accumulation of circulating current can directly trigger overcurrent protection and damage power units.
3. Engineering-Level Suppression Measures (Practical Application Preferred)
✔ Hardware Wiring: The length and diameter of the AC cables from each inverter to the AC busbar must be strictly consistent. AC outgoing lines should be as short as possible to reduce impedance deviation; all inverter PE terminals should be equipotentially connected and uniformly connected to the grounding grid.
✔ Equipment Selection Rules: For parallel connections, inverters of the same model and firmware version are preferred; direct parallel connection of inverters from different series or brands is prohibited (e.g., SUN2000 and SUN5000). (Cannot be directly connected in parallel) Huawei Reference.
✔ Control Scheme Selection:
  • With Parallel Communication Bus (CAN/RS485 Master-Slave Synchronization): The master sends a synchronization reference, and the slave follows the voltage phase and carrier synchronization. This is the preferred choice for parallel grid connection in industrial and commercial applications;
  • No Communication Droop Control: Suitable for communication failure redundancy and remote microgrids; it balances power through virtual impedance and droop coefficient, but places higher demands on line impedance design. IET Research Reference;
✔ Protection Configuration: Each inverter is equipped with an independent AC circuit breaker on the AC side. Multiple inverters are prohibited from sharing a single main switch, facilitating individual unit isolation maintenance and suppressing closing inrush current.
⚡ Quick On-Site Diagnosis Techniques: Connect inverters in parallel under no-load (disconnect the photovoltaic DC input) and observe the AC output current of each unit. If the no-load current is significantly non-zero, it's basically due to excessive circulating current.
SECTION II Communication Conflicts: Bus Fault, ID Duplication, Signal Interference

Parallel systems rely on the communication bus for synchronization, power sharing, and fault linkage. Communication abnormalities will directly lead to disconnection of parallel units and uneven current distribution.

1. Typical Causes of Communication Conflicts
1. Duplicate Device Address IDs: Multiple inverters have the same default ID at the factory. After power-on, bus contention occurs, resulting in message corruption and random disconnections. This is a common mistake for beginners.
2. Incorrect Topology Wiring: Star wiring of the bus (each unit has a separate wire to the host); the parallel communication protocol (CAN) requires a daisy-chain topology, while star wiring is prone to signal reflection and conflicts.
3. Simultaneous Wiring of High-Voltage and Low-Voltage Cables: CAN/RS485 communication lines and PV DC cables/AC output cables run parallel or cross each other. High-voltage interference overwhelms the differential signal, causing intermittent communication loss or inconsistent connection.
4. Missing/Excessive Termination Resistors: Incorrect configuration of the CAN bus termination resistors at the beginning and end causes signal oscillation; the bus is too long, exceeding the maximum transmission distance of the protocol.
5. Firmware Version Differences: The communication message formats of old and new firmware are different, making them unable to recognize each other and causing synchronization failure.
2. Troubleshooting and Resolution Process
1 Plan the ID list, modify the unique slave address for each unit before powering on, and keep accurate label records;
2 Run communication lines through separate shielded conduits, keep them away from AC/DC power cables, and ground the shielding layer at one end;
3 Strictly implement daisy-chain wiring, connect 120Ω terminating resistors at both ends of the bus, and do not add them at intermediate nodes;
4 Before expanding capacity by adding new inverters, upgrade the firmware of the entire parallel unit to the same stable version;
5 Reserve communication bus redundancy; important energy storage PCS clusters can adopt a dual communication bus scheme to improve reliability.
Supplement — Communication Differences between Grid-Connected Inverters and Off-Grid Hybrid Inverters:
Many grid-connected string inverters (such as SUN2000) do not require a parallel CAN bus and rely on grid synchronization; hybrid energy storage inverters and off-grid microgrid inverters connected in parallel must be equipped with dedicated parallel communication lines, which cannot be omitted.
SECTION III Phased Expansion Design Scheme: Avoiding Early-Stage Planning Pitfalls

Overseas projects often adopt phased construction: a portion of inverters are installed in the first phase, with subsequent expansions based on funding and electricity load. Without a unified design in the early stages, later additions may encounter issues such as inability to parallelize, uncontrolled loops, and insufficient bus capacity.

1. Four Dimensions That Must Be Reserved in the Early Design
1. Inverter Selection with Parallel Connection Capacity Reserved
Before purchasing, verify the maximum number of inverters that can be paralleled in the manual; do not exceed the manufacturer's specified parallel capacity. Some models only support a maximum of 6 or 9 units in parallel, and cannot be stacked indefinitely.
2. AC Busbars, Switches, and Cables Selected Based on Final Total Capacity
The busbars of the combiner cabinet, the main circuit breaker, and the cables to the grid connection point should be designed according to the total power and short-circuit current after all expansions are completed; do not purchase only based on the first phase capacity, as this will prevent future modifications. Each inverter should have an independent branch switch for easy access to additional units later.
3. Reserved Communication Bus Interface
A reserved interface is provided at the end of the daisy-chain bus, allowing newly added inverters to directly connect to the link, avoiding rewiring and interruption of existing communication.
4. DC-Side Matching Design (Key to PV-Storage Hybrids)
• Pure PV Grid-Connected Parallel: Each inverter has an independent MPPT (Multi-Level Photovoltaic Test Platform), and string configurations do not need to be identical, but string specifications and voltages within the same inverter must be matched.
• Parallel with Energy Storage PCS: The DC battery bus requires BMS and fuses selected based on the total charge/discharge power. When multiple PCS are connected in parallel sharing a battery cluster, unified scheduling by a cluster controller is necessary to prevent multiple BMSs from competing for charging and discharging.
2. Standard Procedures for Capacity Expansion and Commissioning (On-site Commissioning Checklist)
Step 1: Complete the hardware wiring of the new inverter, verify the AC phase sequence, outgoing line length, and grounding;
Step 2: Modify the communication ID of the new equipment, upgrade the firmware to be consistent with the original units;
Step 3: Disconnect the grid connection switch of the original parallel group, perform no-load synchronous commissioning, and observe the circulating current and power distribution;
Step 4: Load test: Gradually increase the load, check that the output power of each inverter is evenly distributed according to the capacity ratio, with no uneven load;
Step 5: Fault simulation test: Shut down one inverter individually, and the remaining units smoothly take over the load without grid disconnection or impact;
Step 6: Power quality test: Harmonics and voltage imbalance meet local grid connection standards (Russian GOST, IEC, etc.) before long-term grid connection operation.
3. Unrecommended Expansion Practices (Avoiding Pitfalls)
✖ Directly adding inverters of different models and power ratings in parallel later;
✖ Arbitrarily laying the AC output lines of new inverters, mismatching the original cable impedance;
✖ Directly connecting high-power loads to the grid without upgrading communication or performing synchronous no-load testing during expansion.
SECTION IV Parallel System Operation and Acceptance Checklist (For EPC & O&M Teams)
Item Acceptance & Verification Standard Status
01 All inverter models and firmware versions must be consistent; the number of inverters in parallel must be ≤ the manufacturer's maximum limit. ☐
02 AC outgoing line length and wire diameter must be symmetrical; PE equipotential bonding is required. ☐
03 CAN/485 communication: daisy-chain, unique ID, terminating resistor, and shielded wiring must comply with regulations. ☐
04 No-load parallel test: circulating current is within the manufacturer's allowable range; there is no continuous bias current. ☐
05 Load distribution test: power distribution deviation is within ±5%. ☐
06 Single-unit failure exit test: the system switches smoothly without triggering grid protection. ☐
07 The monitoring platform can read the voltage, current, and alarm logs of each inverter individually. ☐
V. Conclusion

The core logic of multi-inverter parallel operation is not simply power aggregation, but a unified approach encompassing synchronous control, impedance matching, and communication coordination. The root cause of circulating current is the asymmetry between voltage differential and line conditions; communication conflicts mostly stem from oversights in cabling, ID, and firmware management; and expansion failures are primarily due to a lack of planning for end-stage capacity in the initial design.

In weak grid overseas scenarios such as the CIS and Africa, the stability of the parallel system directly determines the power plant's grid connection acceptance and long-term availability. Standardized parallel schemes and standardized commissioning procedures can significantly reduce on-site rework and lower overseas after-sales service costs.